KITCHEN SIZES & CLEARANCES · CALCULATOR · CA-11

Range hood size

Enter your cooktop and the hood you want. The calculator gives the hood width, an airflow estimate in CFM, and a typical duct size and mounting height, by the Home Ventilating Institute’s rates and the hood makers’ own rules. Add your hood’s rating to check make-up air.

THE ANSWER

A range hood should be at least as wide as the cooktop, and over an island 6 in wider, 3 in past each side. For airflow, HVI recommends 100 CFM per foot of cooktop width against a wall and 150 over an island: 250 CFM for a 30 in range. For gas, Broan and Thermador use 1 CFM per 100 BTU of burners, so a 50,000 BTU cooktop calls for about 500 CFM. If the hood you buy can move more than 400 CFM, whatever the estimate, ask whether your code requires make-up air.

Wall hood, per foot100 CFM
Island hood, per foot150 CFM
Gas burners1 CFM / 100 BTU
A 30 in range on a wall250 CFMHVI’s rate, 30 in wide or wider

Size your range hood

Your cooktop and hood
Cooktop or range width
Cooking
BTU
Add up the burners on the spec sheet.
Hood
CFM
The highest CFM on its spec sheet. Make-up air depends on it.
Range
Grill or griddle
Hood width
Duct, typical
Above the cooktop, typical
Make-up air
Airflow250 CFMBy the width of the cooktop (HVI).
HVI rates and makers’ rulesCA-11
  • The calculator needs JavaScript, which is turned off in this browser. The rules it uses are below.

Figure 1. Front view, drawn to scale: your cooktop and the hood, with the band of mounting heights its makers give shaded. Your hood’s manual sets the exact height.

How wide a range hood should be

  • At least as wide as the cooktop. HVI says the hood should match the range; GE, Thermador and Wolf say it may be wider but never narrower.
  • Over an island, 6 in wider: 3 in past the cooktop on each side (Wolf, Thermador). With no wall to guide the smoke, the hood needs the extra capture area.
  • Against a wall, wider helps: Vent-A-Hood suggests 3 to 6 in wider, and Broan suggests 3 in more on each side for high-heat cooking.
HoodWidths makers stockSource
Wall and chimney30 in, 36 in, 42 in, 48 in, 54 in, 60 inWolf, Thermador, Viking, Zephyr, GE
Island36 in, 42 in, 48 in, 54 in, 66 inWolf, Viking, Vent-A-Hood
Under a cabinet24 in to 48 inGE, Vent-A-Hood

From each maker’s installation guide or spec sheets, read 20 October 2026. Under-cabinet hoods are about 19½ to 21 in deep, wall hoods 18½ to 27 in and island hoods 23½ to 34 in (GE, Bosch, Vent-A-Hood, Broan, Thermador, Wolf).

How many CFM a range hood needs

CFM, cubic feet per minute, is how much air the hood moves. There are two rules, and the calculator uses whichever asks for more:

RuleRateA 30 in cooktopA 36 in cooktop
HVI, hood on a wall100 CFM per foot250 CFM300 CFM
HVI, island hood150 CFM per foot375 CFM450 CFM
HVI’s minimum, wall / island40 / 50 CFM per foot100 / 125 CFM120 / 150 CFM
Gas burners (Broan, Thermador)1 CFM per 100 BTU50,000 BTU: 500 CFM; 65,000 BTU: 650 CFM

HVI’s rates are for any fuel. HVI gives no BTU rule; for pro-style cooktops it says to follow the cooktop maker. Broan’s Elite guidelines apply 1 CFM per 100 BTU above 60,000 BTU and 100 CFM per foot below it; its Canadian guide applies it to gas cooktops in general, and Thermador recommends it for its own gas ranges.

  • Electric and induction: at least 100 CFM per foot of cooking surface (Thermador), the same as HVI’s wall rate. Broan’s Canadian guide says 350 to 500 CFM is often enough.
  • Grill or griddle: Thermador adds 200 CFM for a 12 in griddle, 400 for a 24 in griddle or a grill, and 600 for both.
  • Hung high: for its Elite hoods, Broan adds 100 CFM for every 3 in above its recommended 24 to 30 in, or a hood 3 in wider, within its 36 in limit; it does not let any hood go higher than its manual allows.
  • Pro ranges: Wolf suggests 600 CFM for its 30 in gas range, 800 for 36 in ranges and 1,200 for 48 in and 60 in ones. HVI says to follow the range maker for pro-style cooktops, so the calculator marks its estimate provisional there.
  • The code’s floor: a kitchen needs at least 100 cfm of exhaust when it runs on demand, or 25 cfm running all the time (2021 IRC Table M1505.4.4; Table M1505.5 in 2024).
  • Ratings: HVI-certified hoods are tested against duct resistance; a “max blower” figure is measured in open air and runs higher. Compare ducted ratings (Broan).

Duct size

Hood airflowRound duct, typicalExamples
Up to about 400 CFM6 in (or 3¼ × 10 in rectangular)Broan EW56 and B5936SS, GE JVW5301; some under-cabinet hoods use 7 in
About 400 to 600 CFM8 inGE Profile PV976 and UVI7361, Zephyr Venezia, Vent-A-Hood dual blowers
About 600 to 1,500 CFM10 inWolf pro hoods, Broan Elite exterior blowers, Viking 1,200 CFM
Larger blower sets12 inVent-A-Hood’s biggest combinations

A pattern across the makers’ guides, not a rule: each hood’s own collar and instructions set its duct, and every maker says never to make it smaller. Bosch’s 300 CFM chimney hood, for one, asks for 8 in. The calculator shows this typical size for your hood’s rating, or for the estimate when you leave the rating blank.

  • Length: Wolf, Thermador and Viking ask you to keep the run within 50 ft of equivalent length; ZLINE allows 40 ft, Zephyr and Monogram 100 ft. Each round 90° elbow counts as 5 to 17 ft, depending on the maker.
  • Material: the 2021 and 2024 IRC require galvanized steel, stainless steel or copper duct (M1503.4) that discharges outdoors, not into an attic or crawl space (M1503.3). GE, Viking, Thermador and Vent-A-Hood say not to use flexible duct.
  • Recirculating hoods: the IRC allows a listed ductless hood, but HVI says recirculating hoods provide no actual ventilation; they filter and return the air.

Running the duct through walls or the roof, and any electrical work, is a job for a licensed HVAC contractor and electrician; ask your building department about permits.

Make-up air above 400 CFM

A strong hood pushes air out of the house, and the same amount has to come back in. The 2021 and 2024 IRC (M1503.6) ask for make-up air for a hood that can move more than 400 cfm when the home has a fuel-burning appliance inside it that is neither direct-vent nor fan-vented, such as an older gas water heater. The rule goes by what the hood you install can move at its highest setting, not by the airflow you need: a 30 in range against a wall needs about 250 CFM by HVI’s rate, but each of Wolf’s pro hoods comes with at least one 600 CFM blower. The make-up air has to enter the kitchen, or a room or duct system connected to it by permanent openings, through a gravity damper or one that opens automatically when the hood runs (M1503.6.1 and M1503.6.2). Some states go further: South Carolina’s code asks for it on any hood over 400 cfm. Makers say the same: check local code. Wolf and Zephyr let the installer cap a blower at 300 or 400 CFM, or 290, 390 or 590, where codes limit airflow.

How high to mount the hood

HoodAbove the cooktop
Under a cabinet24 to 30 in
Wall chimney24 to 36 in
Island30 to 36 in
Over a pro-style range30 to 36 in

Typical bands from the makers’ installation instructions; your hood’s own manual decides. Every maker, and the reasons they differ, is on range hood height.

Questions people ask

What size range hood do I need?

One at least as wide as your cooktop, 6 in wider over an island, moving at least 100 CFM per foot of cooktop width on a wall or 150 over an island (HVI). For gas, compare 1 CFM per 100 BTU (Broan, Thermador) and take the larger.

How many CFM do I need for a 30 inch range?

250 CFM by HVI’s wall rate, 375 over an island. A gas range with 50,000 BTU of burners calls for about 500 CFM by the BTU rule.

How many CFM for a 36 inch gas range?

300 CFM by HVI’s wall rate, or 1 CFM per 100 BTU of its burners if that is more. Wolf suggests 800 CFM for its own 36 in ranges.

Should a range hood be wider than the stove?

It must not be narrower. Over an island it should be 3 in wider on each side (Wolf, Thermador), and on a wall 3 to 6 in wider helps (Vent-A-Hood).

Does a range hood need make-up air?

It may if the hood can move more than 400 CFM, whatever airflow your cooking needs: the IRC asks for it then when a fuel-burning appliance that is not direct-vent or fan-vented is inside the home, and some states ask for it on every hood over 400 CFM.

Final Takeaway

Choose a hood at least as wide as the cooktop, 6 in wider over an island, that moves at least HVI’s 100 CFM per foot of cooktop on a wall or 150 over an island, or, for gas, 1 CFM per 100 BTU of burners (Broan, Thermador) if that is more. For a pro-style range, the range maker’s figure comes first: Wolf, for one, suggests 600 CFM for its 30 in gas range, far above the width rule, so treat the calculator’s figure there as provisional. Before you buy, check whether the hood’s highest rating is over 400 CFM, since make-up air may then be required, and let the hood’s own manual set its duct size and mounting height.

Main Sources

Checked 20 October 2026; the make-up air rule, HVI’s page and the Wolf and Broan guides rechecked 27 October 2026. The calculator’s totals are our arithmetic from these rules; your hood’s and range’s manuals come first.