A range hood should be at least as wide as the cooktop, and over an island 6 in wider, 3 in past each side. For airflow, HVI recommends 100 CFM per foot of cooktop width against a wall and 150 over an island: 250 CFM for a 30 in range. For gas, Broan and Thermador use 1 CFM per 100 BTU of burners, so a 50,000 BTU cooktop calls for about 500 CFM. If the hood you buy can move more than 400 CFM, whatever the estimate, ask whether your code requires make-up air.
Size your range hood
- The calculator needs JavaScript, which is turned off in this browser. The rules it uses are below.
How wide a range hood should be
- At least as wide as the cooktop. HVI says the hood should match the range; GE, Thermador and Wolf say it may be wider but never narrower.
- Over an island, 6 in wider: 3 in past the cooktop on each side (Wolf, Thermador). With no wall to guide the smoke, the hood needs the extra capture area.
- Against a wall, wider helps: Vent-A-Hood suggests 3 to 6 in wider, and Broan suggests 3 in more on each side for high-heat cooking.
| Hood | Widths makers stock | Source |
|---|---|---|
| Wall and chimney | 30 in, 36 in, 42 in, 48 in, 54 in, 60 in | Wolf, Thermador, Viking, Zephyr, GE |
| Island | 36 in, 42 in, 48 in, 54 in, 66 in | Wolf, Viking, Vent-A-Hood |
| Under a cabinet | 24 in to 48 in | GE, Vent-A-Hood |
From each maker’s installation guide or spec sheets, read 20 October 2026. Under-cabinet hoods are about 19½ to 21 in deep, wall hoods 18½ to 27 in and island hoods 23½ to 34 in (GE, Bosch, Vent-A-Hood, Broan, Thermador, Wolf).
How many CFM a range hood needs
CFM, cubic feet per minute, is how much air the hood moves. There are two rules, and the calculator uses whichever asks for more:
| Rule | Rate | A 30 in cooktop | A 36 in cooktop |
|---|---|---|---|
| HVI, hood on a wall | 100 CFM per foot | 250 CFM | 300 CFM |
| HVI, island hood | 150 CFM per foot | 375 CFM | 450 CFM |
| HVI’s minimum, wall / island | 40 / 50 CFM per foot | 100 / 125 CFM | 120 / 150 CFM |
| Gas burners (Broan, Thermador) | 1 CFM per 100 BTU | 50,000 BTU: 500 CFM; 65,000 BTU: 650 CFM | |
HVI’s rates are for any fuel. HVI gives no BTU rule; for pro-style cooktops it says to follow the cooktop maker. Broan’s Elite guidelines apply 1 CFM per 100 BTU above 60,000 BTU and 100 CFM per foot below it; its Canadian guide applies it to gas cooktops in general, and Thermador recommends it for its own gas ranges.
- Electric and induction: at least 100 CFM per foot of cooking surface (Thermador), the same as HVI’s wall rate. Broan’s Canadian guide says 350 to 500 CFM is often enough.
- Grill or griddle: Thermador adds 200 CFM for a 12 in griddle, 400 for a 24 in griddle or a grill, and 600 for both.
- Hung high: for its Elite hoods, Broan adds 100 CFM for every 3 in above its recommended 24 to 30 in, or a hood 3 in wider, within its 36 in limit; it does not let any hood go higher than its manual allows.
- Pro ranges: Wolf suggests 600 CFM for its 30 in gas range, 800 for 36 in ranges and 1,200 for 48 in and 60 in ones. HVI says to follow the range maker for pro-style cooktops, so the calculator marks its estimate provisional there.
- The code’s floor: a kitchen needs at least 100 cfm of exhaust when it runs on demand, or 25 cfm running all the time (2021 IRC Table M1505.4.4; Table M1505.5 in 2024).
- Ratings: HVI-certified hoods are tested against duct resistance; a “max blower” figure is measured in open air and runs higher. Compare ducted ratings (Broan).
Duct size
| Hood airflow | Round duct, typical | Examples |
|---|---|---|
| Up to about 400 CFM | 6 in (or 3¼ × 10 in rectangular) | Broan EW56 and B5936SS, GE JVW5301; some under-cabinet hoods use 7 in |
| About 400 to 600 CFM | 8 in | GE Profile PV976 and UVI7361, Zephyr Venezia, Vent-A-Hood dual blowers |
| About 600 to 1,500 CFM | 10 in | Wolf pro hoods, Broan Elite exterior blowers, Viking 1,200 CFM |
| Larger blower sets | 12 in | Vent-A-Hood’s biggest combinations |
A pattern across the makers’ guides, not a rule: each hood’s own collar and instructions set its duct, and every maker says never to make it smaller. Bosch’s 300 CFM chimney hood, for one, asks for 8 in. The calculator shows this typical size for your hood’s rating, or for the estimate when you leave the rating blank.
- Length: Wolf, Thermador and Viking ask you to keep the run within 50 ft of equivalent length; ZLINE allows 40 ft, Zephyr and Monogram 100 ft. Each round 90° elbow counts as 5 to 17 ft, depending on the maker.
- Material: the 2021 and 2024 IRC require galvanized steel, stainless steel or copper duct (M1503.4) that discharges outdoors, not into an attic or crawl space (M1503.3). GE, Viking, Thermador and Vent-A-Hood say not to use flexible duct.
- Recirculating hoods: the IRC allows a listed ductless hood, but HVI says recirculating hoods provide no actual ventilation; they filter and return the air.
Running the duct through walls or the roof, and any electrical work, is a job for a licensed HVAC contractor and electrician; ask your building department about permits.
Make-up air above 400 CFM
A strong hood pushes air out of the house, and the same amount has to come back in. The 2021 and 2024 IRC (M1503.6) ask for make-up air for a hood that can move more than 400 cfm when the home has a fuel-burning appliance inside it that is neither direct-vent nor fan-vented, such as an older gas water heater. The rule goes by what the hood you install can move at its highest setting, not by the airflow you need: a 30 in range against a wall needs about 250 CFM by HVI’s rate, but each of Wolf’s pro hoods comes with at least one 600 CFM blower. The make-up air has to enter the kitchen, or a room or duct system connected to it by permanent openings, through a gravity damper or one that opens automatically when the hood runs (M1503.6.1 and M1503.6.2). Some states go further: South Carolina’s code asks for it on any hood over 400 cfm. Makers say the same: check local code. Wolf and Zephyr let the installer cap a blower at 300 or 400 CFM, or 290, 390 or 590, where codes limit airflow.
How high to mount the hood
| Hood | Above the cooktop |
|---|---|
| Under a cabinet | 24 to 30 in |
| Wall chimney | 24 to 36 in |
| Island | 30 to 36 in |
| Over a pro-style range | 30 to 36 in |
Typical bands from the makers’ installation instructions; your hood’s own manual decides. Every maker, and the reasons they differ, is on range hood height.
Questions people ask
What size range hood do I need?
One at least as wide as your cooktop, 6 in wider over an island, moving at least 100 CFM per foot of cooktop width on a wall or 150 over an island (HVI). For gas, compare 1 CFM per 100 BTU (Broan, Thermador) and take the larger.
How many CFM do I need for a 30 inch range?
250 CFM by HVI’s wall rate, 375 over an island. A gas range with 50,000 BTU of burners calls for about 500 CFM by the BTU rule.
How many CFM for a 36 inch gas range?
300 CFM by HVI’s wall rate, or 1 CFM per 100 BTU of its burners if that is more. Wolf suggests 800 CFM for its own 36 in ranges.
Should a range hood be wider than the stove?
It must not be narrower. Over an island it should be 3 in wider on each side (Wolf, Thermador), and on a wall 3 to 6 in wider helps (Vent-A-Hood).
Does a range hood need make-up air?
It may if the hood can move more than 400 CFM, whatever airflow your cooking needs: the IRC asks for it then when a fuel-burning appliance that is not direct-vent or fan-vented is inside the home, and some states ask for it on every hood over 400 CFM.
Final Takeaway
Choose a hood at least as wide as the cooktop, 6 in wider over an island, that moves at least HVI’s 100 CFM per foot of cooktop on a wall or 150 over an island, or, for gas, 1 CFM per 100 BTU of burners (Broan, Thermador) if that is more. For a pro-style range, the range maker’s figure comes first: Wolf, for one, suggests 600 CFM for its 30 in gas range, far above the width rule, so treat the calculator’s figure there as provisional. Before you buy, check whether the hood’s highest rating is over 400 CFM, since make-up air may then be required, and let the hood’s own manual set its duct size and mounting height.
Main Sources
- Home Ventilating Institute, How much ventilation do I need? (read 20 October 2026) and its range hood brochure (2008): 100 CFM per foot of range against a wall and 150 over an island (minimum 40 and 50), a hood as wide as the range, and the cooktop maker’s advice for pro-style cooktops
- 2021 International Residential Code, chapter 15 (M1503 domestic cooking exhaust: discharge outdoors, duct material, make-up air for an exhaust system capable of more than 400 cfm and where it enters, M1503.6 to M1503.6.2; Table M1505.4.4: 100 cfm intermittent or 25 cfm continuous for a kitchen), with the 2024 edition (the same rules; the table is M1505.5), read on UpCodes; South Carolina’s amended M1503.6 as an example of a stricter state rule
- Broan-NuTone: Elite installation and blower selection guidelines (2009: 1 CFM per 100 BTU above 60,000 BTU, height and grill adders), its Canadian guide What is the required CFM (May 2023), the EW56 (2021) and B5936SS (2021) spec sheets, and the US range hood CFM guide
- Thermador, ventilation planning guide (June 2024: width, 1 CFM per 100 BTU, electric and induction, griddle and grill adders, duct size and length)
- Wolf, Pro ventilation hoods design guide (April 2026: widths, island overhang, CFM by Wolf range, duct, height, Code-flex)
- GE Appliances installation instructions: JVW5301 wall chimney hood (February 2026), under-cabinet hoods (April 2022), PV970/PV976 (June 2021) and UVI7361 island hood (March 2023)
- Viking, professional hoods installation guide (2013–2014, the maker’s PDF on AJ Madison); Zephyr, Venezia installation guide (2019); ZLINE, wall range hoods manual (July 2025); Monogram, custom hood inserts (2013); Bosch, HCP hood installation manual (2019)
- Vent-A-Hood, kitchen ventilation guide and specifications and manuals (2016–2026)
Checked 20 October 2026; the make-up air rule, HVI’s page and the Wolf and Broan guides rechecked 27 October 2026. The calculator’s totals are our arithmetic from these rules; your hood’s and range’s manuals come first.